Cálculo de la potencia

Heat losses can be divided into two parts: Transmission losses via parts of the building (roof, walls, etc.) and ventilation losses.

Transmission losses 
The size of transmission losses varies according to the areas of the building parts and insulation. The losses are proportional to the temperature differences between indoor and outdoor air.

Ventilation losses
The ventilation in a building is either mechanical or of the natural type. Mechanical ventilation most often consists of a supply and exhaust air unit that makes heat recovery possible. Natural and involuntary ventilation consists of thermal currents causing warm air to rise and leak through openings and unsealed areas.

Click on the headlines for more information.




Parameters

Floor surface m2 Ceiling, K-value W/m2C
Ceiling surface m2 Floor, K-value W/m2C
Building height m Dimensioned indoor temperature XX
Window surface m2 Dimensioned outdoor temperature C
Mounting height window m Annual averge temperature C
Surface entrance door m2 Internal heat W/m2C
Surface external wall m2 Ventilation/air infiltration Changes/h
Window, K-value W/m2C Temperature gradient C/m
Doors, K-value W/m2C External walls, K-value W/m2C
Night temperature C Air changes, night Changes/h
Time in operation with daytemp. hr/24 Time in operation with nighttemp. hr/24
Days per week in operation Days/week Energy price per kWh
Floor surface m2
Ceiling surface m2
Building height m
Window surface m2
Mounting height window m
Surface entrance door m2
Surface external wall m2
Window, K-value W/m2C
Doors, K-value W/m2C
External walls, K-value W/m2C
Ceiling, K-value W/m2C
Floor, K-value W/m2C
Dimensioned indoor temperature XX
Dimensioned outdoor temperature C
Annual averge temperature C
Internal heat W/m2C
Ventilation/air infiltration Changes/h
Temperature gradient C/m
 
Night temperature C
Air changes, night Changes/h
Time in operation with daytemp. hr/24
Time in operation with nighttemp. hr/24
Days per week in operation Days/week
Energy price per KWh

The output calculation is based on the project data and information that has been submitted by the customer. If necessary information is not available, the calculation may be completed by inserting assumed values.

Frico AB is not responsible for miscalculation as a result of inaccurate data from the customer, lack of information or the use of assumed data.


Valor U, ventanas

Material Valor U [W/m2 °C]
Edificio nuevo  
Ventana de 1+1 hojas (1 hoja exterior y 1 hoja con aislamiento) 2,5
Ventana de 2 hojas (2 hojas con aislamiento) 2,7
Ventana de 2+1 hojas (1 hoja exterior y 2 hojas con aislamiento) 1,0
Ventana de 3 hojas (3 hojas con aislamiento) 1,2
Clase de energía A 0,9
Clase de energía B 1,0
Clase de energía C 1,1
Clase de energía D 1,2
Clase de energía E 1,3
Clase de energía F 1,4
Clase de energía G 1,5
   
Edificio antiguo  
Ventana de 1 hojas 5,0
Ventana de 2 hojas 3,0
Ventana de 3 hojas 2,0
Ventana de 3 hojas (hojas con aislamiento) 1,8
   
Source: EnergimyndighetenEnergifönster  
 

Valor U, puerta

Material Valor U [W/m2 °C]
   
Entrada de corredera con paneles completos 0,8
Entrada de corredera con ventanas y puerta 1,3
Puerta plegable con ventanas 2,2
Puerta plegable totalmente acristalada 3,4
Puerta delantera sencilla sin cristal 1,0
Puerta delantera sencilla con cristal 3,4
Puerta delantera doble sin cristal 0,7
Puerta delantera doble con cristal 1

Valor U, paredes

Material Valor U [W/m2°C]
Edificio nuevo  
Moldura de madera con 15 cm de aislamiento y yeso 0,27
Moldura de madera con 20 cm de aislamiento y yeso 0,25
Moldura de madera con 25 cm de aislamiento y yeso 0,22
Moldura de ladrillo con 15 cm de aislamiento y yeso 0,27
Moldura de ladrillo con 20 cm de aislamiento y yeso 0,24
Hormigón ligero con 15 cm de aislamiento 0,25
Hormigón ligero con aislamiento de 20 cm 0,20
Moldura de chapa metálica con 5 cm de aislamiento 0,80
Moldura de chapa metálica con 10 cm de aislamiento 0,40
Moldura de chapa metálica con 15 cm de aislamiento 0,30
Nueva construcción para casa de baja energía 0,18
   
Warehouse  
Single PVC (900 g) 5,0
Insulated hall (Thermohall) 0,6
   
Edificio antiguo  
Ladrillo sencillo, 12 cm 1,8
Ladrillo de 1 1/2, 18 cm 1,1
Bloque de hormigón ligero, 20 cm 0,8
Bloque de hormigón ligero, 30 cm 0,6
Hormigón, 15 cm 2,8
Hormigón con 5 cm de aislamiento 0,8
Hormigón con 10 cm de aislamiento 0,4
Muro de carga con 5 cm de aislamiento 0,8
Muro de carga con 10 cm de aislamiento 0,4
Muro de carga con 15 cm de aislamiento 0,3
Nueva construcción 0,3

Valor U, techo

Material Valor U [W/m2oC]
Edificio nuevo  
Tejado a dos aguas de chapa metálica, con 20 cm de aislamiento 0,24
Tejado a dos aguas de ladrillo, con 20 cm de aislamiento 0,23
   
Edificio antiguo  
Armazón de vigas de hormigón, 15 cm 2,8
Armazón de vigas de hormigón con 5 cm de aislamiento 0,8
Armazón de vigas de hormigón con 10 cm de aislamiento 0,4
Hormigón ligero, 20 cm 0,8
Hormigón ligero, 30 cm 0,6
Tejado de chapa metálica, sin aislamiento 4,0
Tejado de chapa metálica con 5 cm de aislamiento 0,8
Tejado de chapa metálica con 10 cm de aislamiento 0,6
Tejado de chapa metálica con 25 cm de aislamiento 0,2
   
Source: Ekofiber  
 

Valor U, suelo

Material Valor U [W/m2oC]
   
Edificio antiguo < 300 m² 0,40
Edificio antiguo > 300 m² 0,30
Edificio nuevo, suelo con 10 cm de aislamiento 0,20
Edificio nuevo, suelo con 15 cm de aislamiento 0,16
Edificio nuevo, suelo con 20 cm de aislamiento 0,13

Potencia calculada

La potencia calculada de un edificio es la potencia térmica necesaria para mantener la temperatura interior deseada cuando la temperatura exterior se encuentra en su punto más bajo. 

Country/City

Dim. outside temp.
[oC]

 
Australia

 

 
Alice Springs -7  
Brisbane 2  
Canberra -10  
Darwin 13  
Melbourne -3  
Perth 1  
Sydney 2  
Austria    
Innsbruck -27  
Klagenfurt -27  
Vienna -12  
Belgium    
Brussels -17  
Ostend -13  
Virton -18  
Bulgaria    
Sofia -25  
Varna -16  
Croatia    
Dubrovnik -7  
Zagreb -9  
Czech Republic    
Brno -25  
Prague -28  
Denmark    
Copenhagen -24  
Hoyvik -10  
Estonia    
Tallinn -30  
Finland    
Helsinki -33  
Inari -42  
France    
Bordeaux -15  
Lyon -21  
Marseilles -17  
Paris -15  
Germany    
Berlin -22  
Frankfurt -24  
Hamburg -29  
Hannover -29  
München -30  
Greece    
Athens -6  
Thessaloniki -10  
Hungary    
Budapest -23  
Debrecen -28  
Iceland    
Reykjavik -17  
Ireland    
Cork -9  
Dublin -12  
Italy    
Cagliari -2  
Milan -11  
Naples -4  
Palermo 0  
Rome -6  
Venice -9  
Latvia    
Riga -28  
Lithuania    
Vilnius -29  
Netherlands    
Amsterdam -25  
Vissingen -20  
Norway    
Bergen -14  
Narvik -20  
Oslo -26  
Spitzbergen -33  
Poland    
Gdansk -24  
Krakow -27  
Poznan -28  
Warszaw -29  
Portugal    
Faro -1  
Lissabon -1  
Porto -4  
Romania    
Arad -30  
Bucharest -32  
Constanta -23  
Russia    
Archangel -41  
Astrakhan -29  
Irkutsk -50  
Moscow -32  
Perm -44  
St Petersburg -33  
Slovak Republic    
Bratislava -23  
Kosice -27  
Slovenia    
Ljubljana -28  
Spain    
Almeria 0  
Barcelona -7  
Madrid -10  
Santander -4  
Seville -3  
Switzerland    
Bern -20  
Geneva -18  
Zürich -23  
Turkey    
Ankara -25  
Istanbul -9  
Izmir -11  
Kars -37  
Samsun -7  
Ukraine    
Simferopol -21  
Kiev -25  
United Kingdom    
Belfast -13  
Birmingham -12  
Cardiff -17  
Edinburgh -9  
London -10  
Plymouth -9  
 

Temp. anual media

Country/City

DUT
oC

Mean annual temperature
[oC]
Australia

 

 
Alice Springs -7 20
Brisbane 2 20
Canberra -10 13
Darwin 13 28
Melbourne -3 15
Perth 1 18
Sydney 2 17
Austria    
Innsbruck -27 9
Klagenfurt -27 8
Vienna -12 10
Belgium    
Brussels -17 10
Ostend -13 10
Virton -18 9
Bulgaria    
Sofia -25 12
Varna -16 13
Croatia    
Dubrovnik -7 16
Zagreb -9 6
Czech Republic    
Brno -25 9
Prague -28 8
Denmark    
Copenhagen -24 8,5
Hoyvik -10 7
Estonia    
Tallinn -30 5
Finland    
Helsinki -33 5
Inari -42 -1
France    
Bordeaux -15 12,5
Lyon -21 11,5
Marseilles -17 14
Paris -15 12
Germany    
Berlin -22 9
Frankfurt -24 10,5
Hamburg -29 9
Hannover -29 9
München -30 8
Greece    
Athens -6 18
Thessaloniki -10 16
Hungary    
Budapest -23 11
Debrecen -28 10
Iceland    
Reykjavik -15 5
Ireland    
Cork -9 10
Dublin -12 9,5
Italy    
Cagliari -2 17,5
Milan -11 14
Naples -4 15,5
Palermo 0 18
Rome -6 16
Venice -9 14
Latvia    
Riga -21 5,5
Lithuania    
Vilnius -29 6
Netherlands    
Amsterdam -25 10
Vissingen -20 10
Norway    
Bergen -14 8
Narvik -20 4
Oslo -26 6
Spitzbergen -33 -4
Poland    
Gdansk -24 8
Krakow -27 9
Poznan -28 8,5
Warszaw -29 8,5
Portugal    
Faro -1 18
Lissabon -1 16,5
Porto -4 14,5
Romania    
Arad -30 11
Bucharest -32 11
Constanta -23 11,5
Russia    
Archangel -41 0,5
Astrakhan -29 10
Irkutsk -50 -2
Moscow -32 4,5
Perm -44 2
St Petersburg -33 4,5
Slovak Republic    
Bratislava -23 10,5
Kosice -27 9
Slovenia    
Ljubljana -28 10
Spain    
Almeria 0 18
Barcelona -7 16,5
Madrid -10 14
Santander -4 14
Seville -3 19
Switzerland    
Bern -20 5
Geneva -18 7,5
Zürich -23 4
Turkey    
Ankara -25 12
Istanbul -9 14
Izmir -11 17,5
Kars -37 4
Samsun -7 14
Ukraine    
Simferopol -21 11
Kiev -25 8
United Kingdom    
Belfast -13 9
Birmingham -12 9,5
Cardiff -17 10,5
Edinburgh -9 9
London -10 10,5
Plymouth -9 11
 

Calor interior

Edificio W/m2 W/empleado
Tienda 15  
Cafetería 15  
Oficina 10-20 100
Centro deportivo 10  
Panadería 30  
Planta de laminación de acero 50-70  
Taller de coches 15  
Taller mecánico 20  
Taller de mecánica pesada 50  
Chapa metálica/soldadura 25  

Infiltración

 
Material Valor U [W/m2oC]
   
Edificio antiguo < 1000 m² 0,4
Edificio antiguo > 1000 m² 0,2
Edificio nuevo < 1000 m² 0,3
Edificio nuevo > 1000 m² 0,1

Gradiente de temperatura

El aire caliente es más ligero que el aire frío y se acumula en el punto más alto del interior del edificio. Como resultado, se producen diferencias de temperatura entre el suelo y el techo.

El gradiente de temperatura (°C/m) es una medida del aumento de temperatura por metro de altura y varía en función del sistema de calefacción y la estación. 

Calefacción Gradiente de temperatura
Convectores 2-2,5 oC/m
Aerotermos 2-2,5 oC/m
Radiadores 1,2-1,7 oC/m
Paneles radiantes 0,2-0,4 oC/m
Calefacción por suelo ~0,1 oC/m
Gradientes de temperatura de distintos tipos de calefacción a plena potencia.

Output Calculation

Heat loss
Through the floor w
Through the ceiling w
Through the windows w
Through the doors w
Through external walls w
Total transmission losses w
Ventilation losses w
 
Total losses
 
w
Internal heat w
Results
Calculated output kw
Output / m2 W/m2
Output / m3 W/m2
Energyloss

Daytime

Floor kWh/year
Roof kWh/year
Windows kWh/year
Doors kWh/year
Outer walls kWh/year
Ventilation kWh/year
Total kWh/year

Nighttime/weekend

Floor kWh/year
Roof kWh/year
Windows kWh/year
Doors kWh/year
Outer walls kWh/year
Ventilation kWh/year
Total kWh/year

Total losses kWh/year
Internal heat kWh/year

Total requirements kWh/year
Yearly costs /year

The output calculation is based on the project data and information that has been submitted by the customer. If necessary information is not available, the calculation may be completed by inserting assumed values.

Frico AB is not responsible for miscalculation as a result of inaccurate data from the customer, lack of information or the use of assumed data.